Siemens S7

The Siemens S7 connector (S7) communicates directly with Siemens S7 programmable logic controllers (PLCs). It lets you read and write PLC memory areas using raw memory addresses or human-readable variable aliases.

This connector requires instance creation before you can manage connection states and configure variable polling.

TIA Portal configuration

Before connecting, retrieve the IP address, rack number, and slot number from your TIA Portal project configuration.

IP address

Select the PLC in the TIA Portal project tree. Open the Properties tab below and navigate to PROFINET interface > Ethernet addresses to identify the configured IP address.

Rack and slot

S7-1200 and S7-1500 controllers typically use rack 0 and slot 1. For classic S7-300 and S7-400 hardware, open Device configuration to verify the CPU position. The processor is usually on rack 0, slot 2.

Enable PUT and GET communication

Configure the controller to permit PUT and GET communication:

  1. Right-click the controller and select Properties.

  2. Navigate to Protection & Security > Connection mechanisms.

  3. Select Permit access with PUT/GET communication from remote partner.

  4. Compile and download the updated hardware configuration to the PLC.

Connection management

Typically you first install the Siemens S7 connector within an Agent. That way you can connect your cloud platform to your on-premises shopfloor PLCs.

create

Creates an S7 client instance. The connection details follow in connect.

Parameters

None.

Output

Returns the name of the created instance.

connect

Establishes a connection to the target PLC.

Parameters

Input
Key
Description
Type

options

host

The IP address or hostname of the PLC.

string

port

The communication port of the PLC. Default 102.

integer

rack

The physical rack position of the CPU. Default 0.

integer

slot

The slot position of the CPU. Default 1.

integer

timeout

The connection timeout in milliseconds. Default 5000.

integer

Output

Returns true when the connection succeeds. Throws an error on failure.

Example

disconnect

Terminates the active TCP connection session with the PLC.

Parameters

None.

Output

Returns true on successful disconnection, including when no connection exists.

getStatus

Queries the current connection state of the instance.

Parameters

None.

Output

Returns 'disconnected', 'connecting', or 'connected'.

delete

Removes the instance and its configuration.

Irreversible action

Parameters

None.

Output

Returns true upon removal.

Variable addressing and dictionary

The address dictionary is an optional convenience layer. Functions like addItems and writeItems accept aliases, raw PLC addresses, or a mix of both: the connector first checks whether a string is an alias in the dictionary and otherwise treats it as a direct address. See Memory address syntax for the address format.

setAddressDictionary

Configures the connector instance with an address dictionary. This lets you map human-readable aliases to raw PLC addresses for use in subsequent polling or data transactions.

Polling configuration reset

Parameters

Input
Description
Type

dictionary

An object mapping human-readable aliases to raw PLC addresses. Default {}.

object

Output

Returns true on successful registration.

Example

showAddressDictionary

Retrieves the active address dictionary.

Parameters

None.

Output

Returns an object containing the registered address aliases.

Polling list configuration

addItems

Registers variable addresses or dictionary aliases in the background read polling loop.

Parameters

Input
Description
Type

items

A variable address, alias, or array of strings to add to the polling queue.

array or string

Output

Returns true on success.

Examples

Example 1: Register raw memory addresses

Example 2: Register mixed aliases and raw addresses

removeItems

Removes specific variables from the background polling loop.

Parameters

Input
Description
Type

items

A variable address, alias, or array of strings to remove from the polling queue. If omitted, removes all variables.

array or string

Output

Returns true on success.

Example

removeAllItems

Removes all registered variables from the active background polling queue.

Parameters

None.

Output

Returns true on success.

showAllItems

Lists all variables currently in the background polling queue.

Parameters

None.

Output

Returns an array of all raw memory paths or dictionary aliases in the polling queue.

Data operations

readAllItems

Reads the current values of all variables in the polling queue.

Parameters

None.

Output

Returns an object containing the current values of all registered variables. Keys map to the variable names or aliases. Throws an error if reading fails.

writeItems

Writes data updates to one or more variables on the PLC.

Concurrent write constraint

Parameters

Input
Description
Type

items

A variable address, alias, or array of strings to update.

array or string

values

The value or array of values to write. Ensure the array length and order match the items parameter.

array or any

Output

Returns true when the write succeeds. Throws an error on failure.

Examples

Example 1: Write a single variable

Example 2: Write multiple variables

Deprecated functions

The following functions are maintained for backward compatibility. Update your App logic to use the recommended replacements.

Deprecated function
Use instead

initiateConnection

connect

dropConnection

disconnect

Tips and tricks

Memory address syntax

Format memory address strings as AREA,TYPE<BYTE_OFFSET>[.BIT_OR_LENGTH].

Memory areas

  • DB<number> (Data Block) – Shared memory registers for logic, recipes, and process variables (such as DB1,REAL4).

  • I (Inputs) – Read-only registers tracking physical digital and analog inputs.

  • Q (Outputs) – Control registers driving physical outputs.

  • M (Merkers/Internal Memory) – Internal processor flags and global staging variables.

Data layouts

  • Boolean (X) – Single-bit fields (such as DB1,X0.0).

  • Byte (B) – 8-bit integer values from 0 to 255.

  • Char Array (C) – Alphanumeric sequences (such as DB1,C20.10 for 10 sequential characters).

  • String (S) – Siemens S7 strings with standard length headers.

  • Integer (INT) – 16-bit signed integers.

  • Word (WORD) – 16-bit unsigned integers.

  • Double Int (DINT) – 32-bit signed integers.

  • DWord (DWORD) – 32-bit unsigned integers.

  • Real (REAL) – 32-bit floating-point decimals (such as DB1,REAL14).

Error "Object does not exist"

This error means you are reading or writing a Data Block (DB) that either does not exist or is too small in the PLC. Ensure the DB number is correct and that its size in TIA Portal is large enough to hold all your variables.

Handling scrambled strings

If characters returned by the S string type appear scrambled or out of order, the PLC might store a raw character array instead of a standard S7 string. S7 strings contain a header that defines capacity. If the PLC stores raw characters without a header, use the C (Char Array) type to read the text (such as DB1,C0.16).

Reading TIME values

S7 processors store TIME values as signed 32-bit integers tracking milliseconds. To read or write these values, use the DINT data type.